Specifications

Hollow Metal Detention Doors

Specifications

DIVISION ELEVEN – EQUIPMENT

DETENTION HOLLOW
METAL DOORS AND FRAMES SECTION 11191

PART 1 – GENERAL

1.1 SCOPE
Furnish hollow metal security items as shown in the contract drawings and as specified in this Section.

1.02 WORK INCLUDED
Hollow Metal Detention Security Doors, Swinging Type.

Indicate bullet resistance here only if applicable to job. If these are to be fire rated doors indicate the class required, A, B, C, D, or E. Also indicate the operating type required.

Hollow Metal Detention Security Frames (for Class Fire Rated Doors). Frames must meet fire-rating requirements of doors.

View Windows

Window Walls

Guard Enclosures

Control Room Enclosures

Visitor Room Enclosures

Visitor Booths

Access Panels

Hollow Metal Panels Similar in Construction to Security Doors

Other Required Items:

The foregoing list is illustrative of items, which may be included. Items may be deleted or added. However, specifier should list only those items required.

The following items are not to be included in this section:

  • Installation of frames and/or doors.
  • Furnishing and installation of door hardware or rough hardware of any kind.
  • Furnishing and installation of weather-stripping and gasketing.
  • Installation into doors of frames of items furnished by others.
  • Field assembly of spliced frames. *
  • Furnishing of lead lining of doors and/or frames. *

*Include these items in 1.02 if applicable to the project.

1.03 RELATED WORK

  1. Section 03300-Cast-in-Place Concrete:
    Item(s)_____________________________
  2. Section 03346-Concrete Floor Finishing:
    Item(s)_____________________________
  3. Section 034xx-Precast Concrete:
    Item(s)_____________________________
  4. Section 043xx-Masonry System:
    Item(s)_____________________________
  5. Section 05120-Structual Steel:
    Item(s)_____________________________
  6. Section 08700-Hardware:
    Item(s)_____________________________
  7. Section 08800-Hardware:
    Item(s)_____________________________
  8. Section 09900-Field Painting
    Item(s)_____________________________

1.04 TESTING AND PERFORMANCE
Detention security hollow metal manufacturers shall submit to the Architect, twenty-one (21) days prior to bid date, independent testing laboratory report certifying the following minimum performance of 3’0 x 7’0” x 14 gauge minimum, flush door.

  1. Static Load Test
    Under a centrally applied load of 14,000 lbs. At quarter points the maximum midspan deflection shall not exceed 0.58 in. After release of load, deformation shall not exceed 0.015 in.Refer to figure 4 for illustrations of test set up.
  2. Rack Test
    Under a concentrated load of 7,500 lbs. On one unsupported corner of door, the maximum deflection shall not exceed 3.5 in. There shall be no bucking or failure of welds.Refer to figure 5 for illustration of test set up.
  3. Impact Load Test
    1. 1. A 3’0” x 7’0” door frame and hardware assembly shall be constructed and rigidly mounted in the vertical position so that the door and locking hardware are operable. The door shall swing 1 ½ pairs of full mortised butt hinges and shall be locked using a recognized detention security lock with bolt size not to exceed 2” high 2 ¾” wide and latch throw not to exceed 5/8”.A pocket lock mounted in the door is used because the preparation is the most detrimental to the door construction. By using this type lock the most vulnerable case is being tested.

      Refer to Figure 6 for illustration of door and frame assembly.

    2. A door ram pendulum system capable of delivering consistent impacts of up to 200 ft-lbs shall be constructed so that impacts may be delivered to any area of the assembly.200 ft-lbs is used because it has been established experimentation that a person with an 8 lb. sledge hammer or several persons with a battering ram can develop up to 200 ft-lb. of impact energy per blow.

      Refer to Figure 7 for illustration of ram pendulum system.

    3. The ram pendulum system shall be positioned opposite the door side of the assembly so that the door swings away from the ram. While hanging at rest the ram shall be positioned so that the striking nose just touches the target area of the door. The striking nose of the ram shall be made of C1010 or C1020 low carbon steel. The striking surface area of the nose shall be 4.0 ± 0.04 sq. in.4.0 sq. in. is the approximate striking surface area of an 8 lb. sledgehammer.
    4. With door closed and locked, and the above testing arrangement secured, the following series of impacts shall be delivered to the assembly. The ram shall be raised to height so that when released it will strike the door with 200-ft-lbs. of energy with each impact.
  1. 400 impacts on the door within 6” of the bolt
  2. 50 impacts on the door within 6” of middle hingeA total of 450 blows are used in the test because this is about the maximum number of blows that any one assembly might receive in a 45 to 60 minute time period. This is the time that is usually required to restore order in major riot situation.
  • The door shall remain closed and locked throughout the testing procedure, and the assembly shall not be damaged to the extent that forcible egress can be obtained. After testing is completed the door shall be capable of being unlocked and operated to provide egress.
  • Removable Glazing Stop Test
    1. A rectangular view window test frame shall be constructed with a glass opening size of 28” x 33” + 1”. The frame shall be constructed of commercial quality steel meeting ASTM 366 or A 569, 12-gauge maximum.The test frame opening size was chosen because it is representative of the view window sizes of average control rooms, day rooms and guard stations. 12 gauge is customarily the maximum used for detention frames.

      Refer to figure 8 for test frame dimensions.

    2. A steel plate of 3/8” minimum thickness shall be glazed in place using the specified glass stop method.A steel plate is used in lieu of security glass for testing purposes. The plate acts as a median through which impact energy is transferred to the removable glass stops.

      Refer to figure 9 for details of the test frame assembly and to figure 10 for details of the glass stop and reinforcement.

    3. The test frame assembly shall then be rigidly fixed in the horizontal position with the removable glass stop on the lower side.
      1. A target on the topside of the 3/8” plate shall be marked in one corner no more than 6” away from the stops.An attacker will most likely strike the glass at a corner knowing that it is the weakest point, hence the location of a test target near the corner. Also, striking the plate in the center will allow dissipation of much of the impact energy through deformation of the plate and vibration. Striking it in the corner will transmit the maximum amount of impact energy from the ram to the stops, again producing the most vulnerable condition.
    4. Impact dart capable of developing up to 400 ft-lbs of impact energy to the plate and whose impact surface area 4 sq. is in shall be positioned to strike the target.Impact energy of 400 ft-lbs. per blow is used because there is a high impact resistant glass on the market which resists 400 ft-lbs. of impact energy. This will ensure that regardless of the glass used, the removable stops will be at least as impact resistant as the glass.

      Refer to figure 11 for illustration of test set up.

    5. Ten (10) impacts of 400 ft-lbs. each shall be delivered to the target. The removable glass stops shall remain undamaged and the 3/8” plate shall remain firmly in place. There shall be no more than one (1) broken fastener in the assembly after impact testing.High impact resistant glass is usually tested at one to five impacts are applied in this case to ensure that the stops have adequate impact fatigue strength and also to more closely simulate actual field conditions.
  • Bullet Resistance
    1. Where specified on individual openings, bullet resistance shall be certified by underwriters Laboratories, Inc. under their testing procedure described in UL Standard #752. The bullet resistance rating shall be “super-power small arms: 44 Magnum Revolver.”The 44 Magnum Revolver is used in this specification because it is the most powerful commonly available handgun. According to prison officials, High Armory handguns, however, could be obtained in a riot situation. For this reason it is recommended that all doors which are indicated on his door schedule to be bullet resistant, and be certified for the 44 Magnum Revolver.
    2. As an alternate, a sample door shall be constructed, tested, and certified by a qualified independent testing laboratory in accordance with the test procedure outlined UL Standard #752. In this case test reports shall include complete descriptions of the test procedure and results. Firearms and ammunition used shall be certified as being correct with respect to bullet caliber, weight, muzzle velocity, and muzzle energy.
  • Test Reports
    All test reports shall include details of test samples and details of photographs of the testing apparatus. The test samples shall be retained at the manufacturer’s facilities for possible inspection.
  • Job Site Door Check
    At the owner’s option, a door at the job site may be selected at random, sawed in half to verify if the door was constructed in accordance with test report details. If the door details do not conform to the specification, the door will be replaced at the manufacture’s expense and replaced with doors that meet the requirements.

1.05 QUALITY ASSURANCE

  1. Manufacturer’s Qualification
    In order to be approved as an acceptable bidder, each manufacturer, without exception shall submit the following materials twenty-one (21) days prior to bid date.

    1. List of representative detention projects for which the manufacturer has supplied detention security hollow metal products including dates of project completion.
    2. One (1) copy of each of all test reports certifying the successfully completion of testing procedures as specified in 1.04.
  2. Quality Criteria
    1. Labeled doors and frames shall be provided for those openings requiring fire protection ratings as determined and scheduled by the Architect. Such doors and frames shall be constructed as tested and approved by Underwriters Laboratories or other recognized testing agency having a factory inspection service.
    2. If any door or frame specified by the Architect to be fire-rated cannot qualify for appropriate labeling because of its design, hardware or any other reason, the Architect shall be so advised before fabrication work on that item is started.
    3. Fabrication methods and product quality shall meet standards set by the Hollow Metal Manufacturers Association, HMMA, a Division of the National Association of Architectural Metal Manufacturers, NAAMM.Refer to NAAMM’s Hollow Metal Manual and Fire-Rated Hollow Metal Doors and Frames.

1.06 REFERENCES

  1. ASTM A 366-72 (1979) Specification for Steel, Carbon, Cold-Rolled Steel, Commercial Quality.
  2. ASTM A 569-72 (1979) Specification for Steel, Carbon, (0.15 Maximum Percent), Hot-Rolled Sheet and Strip Commercial Quality.
  3. ASTM B 117-73 (1979) Salt Spray (Fog) Testing
  4. ASTM D 1735-62 (1980) Water Fog Testing of Organic Coatings.
  5. NAAMM Fire-Rated Hollow Metal Doors and Frames, Second Edition, Nov 1983.
  6. NAAMM Hollow Metal Manual, February 1987.
  7. UL 752 Bullet-Resisting Equipment, October 5, 1979.

ASTM
American Society for Testing and Materials
1916 Race Street
Philadelphia, Pennsylvania 19103

NAAMM
National Association of Architectural Metal Manufacturers
600 South Federal Street
Chicago, Illinois 60605

UL
Underwriters Laboratories
333 Plingsten Road
Northbrook, Illinois 60062

1.07 SUBMITTALS

  1. Shop Drawings
    1. Show door and frame elevations and section.
    2. Show listing of opening descriptions including locations, gauges, anchors, and finish hardware sets.
    3. Show fabrication and installation drawings where applicable.
    4. Show location and details of all openings.
  2. Samples
    1. Door: 1’0”x 1’0” corner section with hinge mortise and reinforcement showing internal construction.
    2. Frame: 1’0”x 1’0” Corner section showing welding joint of head to jamb. Include hinge mortise, reinforcement and plaster guard in one rabbet, and glazing stop applied as specified in the opposite rabbet. Glazing stop must be applied in both head and jamb section to show corner joint.

1.08 WARRANTY
All hollow metal work shall be warranted from defect in workmanship and qualify for a period of one (1) year from shipment.

PART 2-PRODUCTS

2.1 HOLLOW METAL DOORS

  1. General: Detention-type hollow metal doors to be furnished and installed under this section shall be as indicated on the Detention Door Schedule. Frames for detention hollow metal doors will be furnished and delivered to the jobsite by the Detention Equipment Contractor and set in place by the General Contractor at no cost to the Detention Equipment Contractor. Threshold for exterior hollow metal swinging doors in this section shall be furnished and installed by the Detention Equipment Contractor. Locks and hardware for doors provided under this section shall be as indicated on the Detention Hardware Schedule.
  2. Manufacturers:
    1. Overly Door
    2. Sweeper Metal
    3. CECO
  3. Construction:
    1. Detention-type hollow metal doors shall have a thickness of 2” (nominal). Doors shall have 1/8” side clearance with proper bevel to operate without binding. Furnish all accessory items as required for a complete installation.
    2. Doors shall be custom-made, of the types and sizes shown on approved shop drawings, and shall be prepared for hardware in accordance with the manufacturer’s recommendation and the final approved Detention Hardware Schedule. Doors shall be constructed using commercial-quality cold-rolled steel that complies with ASTM A366. The steel used shall be free from scale, pitting, coil breaks, or other surface blemishes. The steel shall also be free of buckles, waves, or any other defects caused by the use of improperly leveled sheets. Door face thickness shall be 12 gauge.
    3. Door edge seams shall be continuously welded and finished smooth such that there are no visible seams. Doors shall be strong, rigid, and neat in appearance, free from warpage or buckle. Edge bends shall be true and straight and of minimum radius for the gauge metal used.
    4. Doors shall be stiffened by continuous vertically formed steel sections that, upon assembly, shall span the full thickness of the interior space between door faces. These stiffeners shall be 16-gauge minimum, spaced such that the vertical interior webs shall be no more than 4” o.c. and securely fastened to both face sheets by spot welds spaced a maximum of 2 ½” o.c. vertically and by welding together 18” to 24” o.c. on one side the full height of the door. Spaces between stiffeners shall be filled with 3 lbs./cu. Ft. fiberglass or mineral rock wool batt-type material. If the manufacturer must use heavier materials and/or closer stiffener and weld spacings to meet the performance criteria set forth in Subparagraph 1.4f, “Certification,” of this section, he must use them in the door construction for this project. Door construction details must be submitted for approval as part of the submittal drawings.
    5. Vertical edge at strike shall be a continuous steel channel, not less than 10 gauge, extending the full length of the door with strike reinforcements as an integral part of the channel construction. Vertical edge at hinge shall be reinforced by a continuous steel channel, not less, than 7 gauge extending the full length of the door with hinge reinforcements as an integral part of channel construction. Non-continuous channel at lock edge shall be acceptable only to accommodate lock preparation. In this case, hardware reinforcements shall be welded to the channel such that they become an integral part of the channel. The top and bottom edges shall be closed with a continuous channel, also not less than 10 gauge spot-welded to both face sheets a maximum of 3” o.c. The corners of each intersection of channels shall overlap and be continuously welded to the full perimeter of the intersection.
    6. Top and bottom channel shall be fitted with an additional flush closer plate of not less than 12 gauge. The flush closing plate shall be welded in place at the corners and 1 ½” long welds 12” o.c. Installation of closer plate using screws, detention or otherwise, shall be deemed unacceptable. The end channel and flush closer plate shall be installed such that they are permanent and nonremovable.
    7. Edge profiles shall be provided on both vertical edges of door as follows:
      1. Single-acting Doors: Beveled 1/8” in 2”.
      2. Horizontal track doors or equivalent-square profile
    8. Hardware Reinforcements:
      1. Doors shall be mortised, reinforced, drilled, and tapped at the factory for completely templated, mortised hardware in accordance with the final approved hardware schedule and templates provided by the hardware supplier. Where surface-mounted hardware is to be applied, door shall be reinforced, drilled, and tapped in accordance with final approved hardware schedules and templates by installer.
      2. Minimum gauges for hardware reinforcements shall be as follows.
        1. Full mortised hinges and pivots: 7-gauge
        2. Surface-applied maximum security: minimum thickness to equal major diameter screw, but no less than ¼” plate.
        3. Reinforcements for lock fronts, concealed holders, or surface: 7 gauge
        4. Mounted closures: 7-gauge
        5. Internal reinforcements for all other surface-applied hardware: 7-gauge
      3. Angle, flat or offset strap reinforcements that are welded to the inside edge of the door or to perimeter channel shall be unacceptable for hinge or strike reinforcements. All reinforcements for mortised hardware occurring in the edge of the door shall be integral to the edge channel except where hardware type will not permit.
      4. Doors containing manual prison locks (80 series) will be flush-mounted with the face sheets of the door (refer to detail)
      5. Doors that require additional hardware (e.g. food pass openings, locks, and hinges) will be as shown on detail.
    9. Doors shall be provided with steel moldings to secure glazing in accordance with glass sizes and thickness shown with a minimum 1” glass engagement.
      1. Fixed glass stops molding shall be pressed steel offset surface-mounted of not less that 10 gauge with tight-fitting mitered or coped corner joints, and secured with #1/4-20 Grade 8 Torx pinhead buttonhead screws spaced 6” o.c. maximum with a maximum spacing of 2” from the ends of the stops.
      2. Removable glass stops specified in paragraph 2.3 1.3 shall meet performance criteria designated in the performance section of this specification.
      3. Removable stops shall be on the side opposite the area of inmate confinement or where they are likely to be unsupervised. Owner shall provide this information before fabrication can begin.
    10. Security Louver Design: Door face sheets shall be furnished with 1” wide horizontal slats of length equal to be designated louver width, and spaced 1” apart. The number of slats shall be determined by the designated louver height. The louvers shall be of a 12 gauge Z-type construction and weld 4” o.c. to the inside face sheets along the 1” strips between the slats. Twelve (12) gauge vertical channels shall be welded in place on each end of the louver slats and shall extend above and below the slats 4” The Z louvers shall be continuously welded at each end to the 12 gauge channels. Upon completion, the louvers shall become an integral door construction. Full width x full height face sheet louver cutouts shall be unacceptable. Louvers shall meet impact load tests as designated in the performance section of this specification.
    11. Food Pass Openings: The food pass openings shall be flush opening fabricated using interior channels. 12 gauge minimum securely welded to the inside of both face sheets. The four corner seams shall be continuously arc welded and dressed smooth. The finished opening shall be constructed such that it cannot be dismantled.
      1. The food pass shutter shall be constructed as per detail. The food pass shutter shall be furnished with a continuous heavy duty hinge by door manufacturer and one each food pass lock as specified in the security hardware sets by hardware supplier.
      2. Shutter shall be chemically treated for maximum paint adhesion a shop coat of rust inhibitive primer.
    12. Speaking Devices: The speaking device shall consist of a rectangular pattern of round holes, no more than ¼” diameter, in both face sheets directly across from each other. The minimum size of the rectangular hole pattern shall be 1” high x 4” wide with a minimum of two rows of holes spaced no more than 1” o.c. the interior of the door between the hole patterns shall be baffled using pressed steel section, 14 gauge, such that no objects can be passed through.
    13. Finish: After fabrication, all tool marks and surface blemishes shall be filled and sanded as required to make both faces and both vertical edges smooth and free from irregularities. After appropriate preparation, all exposed surfaces shall receive two shop coasts of a rust inhibitive primer which meets or exceeds ASTM B 117 salt spray for 150 hours, and ASTM D 1735 water fog test for organic coatings for 200 hours, and which is fully cured prior to shipment.

2.02 HOLLOW METAL FRAMES

  1. Materials: Frames for exterior openings shall be constructed of commercial quality, Cold-rolled steel which complies with ASTM A 366. As an alternate commercial quality, hot-rolled/pickled-and-oiled steel may be used which complies with ASTM A 569. In either case, the steel shall be free of scale, pitting, coil breaks or other surface defects. Metal thickness shall be no less than 12 gauge.
  2. Construction:
    1. Frames shall be constructed of commercial-quality cold-rolled steel that complies with ASTM A366. The steel shall be free of scale, pitting, coil breaks, or other surface defects. Metal thickness shall be .093 or as specified.
    2. Frames shall be custom-made welded units of the sizes and types shown on approved shop drawings. Finished work shall be strong and rigid, neat in appearance, square, and free of defects, wraps, or buckles. Pressed steel members shall be straight and of uniform profile throughout their lengths.
    3. Corner joints shall have contact edges, closed tight with faces mitered and stops either butted of mitered. Corner joints shall be continuously welded and the use of gussets or splice plates will be unacceptable.
    4. Stops: Minimum depth of stops in door openings shall be 1”. For glass and panel openings, stops shall be 1” minimum glass or panel engagement, or as approved by the detention glazing manufacture, to included rabbeted depth of stops.
  3. Loose Glazing Stops:
    1. Pressed steel angle glazing stops shall be no less than 10 gauge. Angle stops shall be mitered or coped and tight fitting at the corner joints.
    2. There shall be individual threaded enclosed fasteners as backup, welded under the frame where loose glazing stops are to be attached. The backup shall pass the test prescribed within this spec section.
    3. The frame under the glazing stops and the inside of the glazing stop shall be chemically treated for maximum paint adhesion and painted with a rust-inhibitive primer prior to installation in the frame.
    4. Stops shall be secured with Torx-head tamperproof machine fasteners where detention glazing is scheduled. Screws shall be Grade 8 buttonhead ¼”-20 x proper length. Locate fasteners not more than 2” from each end of glazing stop and no more than 6” o.c.
    5. Removable stops shall be on the side opposite the area of inmate confinement or where they are likely to be supervised. Owner shall provide this information before fabrication can begin.
  4. Frames for multiple openings shall have mullion members that, after fabrication, are closed tubular shapes conforming to profiles shown and having no visible seams or joints. Joints between faces of abutted members shall be continuously welded and finished smooth.
  5. Hardware Reinforcements and Preparation:
    1. Frames shall be mortised, reinforced, drilled, and tapped for all template mortised hardware only, in accordance with the final approved hardware schedule and templates provided by the hardware supplier. Where surface mounted hardware is to be applied, frames shall have reinforcements only; all drilling and tapping shall be done by others.
    2. Minimum thickness of hardware reinforcing plates shall be as follows:Hinge and pivot reinforcements- ¼” x full width of jambs x 10” in length
      Strike reinforcements- 7 gauge
      Closer reinforcements- 7 gauge
      Flush bolt reinforcements- 7 gauge
      Reinforcements for surface applied hardware- 7 gauge
      Frame reinforcements for glazing stops-individual threaded enclosed
      Fasteners to provide backup and protection from grout.
    3. Hinge and pivot reinforcement shall consist of ¼” x 2” x 10” long straps projection or arc welded in a triangle pattern in three places at each end. The strap shall be additionally reinforced by a 12 gauge unitized stamped mortar box angle reinforcement, which is welded to two places to the inside face of the frame and at each end of the mortar box forming a rigid reinforcement and a tightly closed mortar box.
    4. In case where electrically operated hardware is required, and where shown on approved shop drawings, hardware enclosures and junction boxes shall be provided, and shall be interconnected using UL approved ½” minimum conduit and connectors. Also, where shown on shop drawing, junction boxes with access plates shall be provided to facilitate the proper installation of wiring. Access plates shall be the same gauge as the frame and fastened with a minimum of (4) #8-32 tamperproof machine screws, not exceed 6”o.c.
  6. Floor Anchors:
    1. Floor anchors with two holes for fasteners shall be fastened inside jambs with at least four (4) spot welds per anchor.
    2. Where so scheduled, adjustable floor anchors, providing no less than 2” height adjustment, shall be fastened in place with at least four (4) spot welds per anchor.
    3. Gauge thickness of floor anchors shall be the same as frame.
  7. Jamb Anchors:
    1. Frames for installation in masonry walls shall be provided with adjustable jamb anchors of the strap and stirrup type made from the Frames 7’6” to 8’0” height-5
    2. Frames over 8’0” height-1 anchor for each 18” or frac. Frames for installation in pre-finished masonry or concrete openings shall be punched and countersunk for expansion bolt anchors and provided with hat shaped reinforcements, same gauge thickness as frame, secured in place with at least four (4) spot welds each. The number and spacing of anchors provided shall be as outlined in section (a) above. Concrete anchors and bolts shall be provided by others.
    3. Frames to be installed in pre-finished concrete, masonry or steel openings, but not to be anchored using expansion bolts, shall be constructed and provided with anchoring systems if suitable designs as shown on the approved shop drawings.
  8. Plaster guards made from no less than 26 gauge steel shall be welded in place at all hardware mortises on frames to be set in masonry or concrete openings.
  9. All frames shall be provided with two (2) temporary steel spreaders welded to the feet of the jambs to serve as bracing during shipping and handling. Remove temporary spreaders to set frame at the permanent location.
  10. Loose glazing stops:
    1. Loose channel type glazing stops shall be cold-rolled steel, no less than 12 gauge, butted corner joints and secured to the frame using #8-32 tamperproof countersink machine screws, spaced 9”o.c. minimum.
    2. Where shown on the contract drawings, pressed steel angle glazing stops, no less than 10 gauge, shall be provided. Angle stops shall be mitered or coped and tight fitting at the corner joints, and secured in place using machine screws of the size and spacing necessary to satisfy the performance criteria outlined in section 1.04 (D).
    3. The frame underneath the glazing stops and the inside of the glazing stops shall be chemically treated for maximum paint adhesion and painted with a rust-inhibitive primer to installation in the frame.
  11. Finish: After fabrication, all tool marks and surface imperfections shall be removed, and exposed faces of all welded joints shall be dressed smooth. Frames shall be chemically treated to insure maximum paint adhesion and shall be coated on all accessible surfaces with a rust-inhibitive primer which meets or exceeds ASTM B 117 salt spray for 150 hours, and ASTM D 1735 water fog test for organic coatings for 200 hours, and which is fully cured prior to shipment.

2.03 CLEARANCES AND TOLERANCES

  1. Edge clearances shall be provided as follows:Between doors and frames, at head and jambs: 1/8”
    At door sills where no threshold is used: 3/8” max.
    At door sills where threshold is used: ¾” max. above finished floor*
    Between edges of pairs of doors: 1/8”
  2. Manufacturing tolerance shall be maintained within the following limits:
    1. Frames for single door or pair of doors.
      Width measured between rabbets at the head: Nominal opening width + 1/16”, -1/32”
      Height (total length of jamb rabbet): Nominal opening height. + 3/64”
      Gross sectional profile dimensions:
      Face +1/32”
      Stop +1/32”
      Depth+1/32”
      Throat+1/16”. Frames overlapping walls to have throat dimension 1/8” greater than dimensioned wall thickness to accommodate irregularities in wall construction.*Finish floor is defined as the top surface of the floor, except when resilient tile or carpet is used, when it is the top of the concrete slab. Where the carpet is more than ½” thick, allow ¼” clearance.

      Hardware cutout dimensions:
      Template dimensions + 0.015’’, -0

    2. Doors
      Width: +3/64’’
      Height: +3/64’’
      Thickness: +1/16’’
      Hardware cutout dimensions:
      Template dimensions + 0.015’’.-0
      Hardware location : +1/32’’

PART-3 EXECUTION

3.01 SITE STORAGE AND PROTECTION OF MATERIALS

  1. The General Contractor shall see that any scratches or disfigurement caused in shipping, or handling are promptly cleaned and touched up with a rust inhibitive primer, and that materials are properly stored on planks or dunnage, in a dry location, and covered to protect them from damage.
  2. Doors shall have their wrappings or covering removed upon delivery at the building site and shall be stored in a vertical position, in a dry location, spaced by blocking to permit air circulation between them.

3.2 INSTALLATION

It shall be the responsibility of the general contractor to perform the following:

  1. Prior to installation all frames must be checked and corrected for size, swing, squareness, alignment, twist and plumbness. Permissible installation tolerance shall not exceed the following:Squareness + 1/16”: measured on a line, 90 degrees from one jamb, at the upper corner of the frame at the other jamb.

    Alignment + 1/16”: measured on jambs on a horizontal line parallel to the plane of the wall.

    Twist + 1/16”: measured at face corners of jambs on
    parallel lines perpendicular to plane of the wall.

    Plumbness + 1/16”: measured on the jambs at the floor.

  2. Frames jambs, where possible, are to be fully grouted to provide added security protection against battering; wedging, spreading and other means of forcing open the door.
  3. Proper door clearances must be maintained in accordance with 2.03 of these specifications, except for special conditions otherwise noted. Where necessary, metal hinge shims, furnished by the General Contractor, are acceptable to maintain clearances.
  4. Hardware must be applied in accordance with hardware manufacturers’ templates and instructions.

Note to Architect: Proper installation is essential to the proper performance of the doors and frames. The requirements for proper installation are given in the preceding paragraphs. However, it is important to recognize that installation is not normally the responsibility of the hollow metal manufacturer. For this reason the requirements for installation of hollow metal doors and frames should be in the section of the specifications where installation of work is specified.

SPECIAL INFORMATION REGARDING DETENTION EQUIPMENT

  1. Detention Equipment Contractor shall be responsible for the execution of his work in strict accordance with contract drawings and specifications. Other contractors shall likewise be responsible for their work being in strict accordance with dimensions and construction shown on contract drawings and shall be responsible for and shall correct their errors in the work. Detention Equipment Contractor shall call to the attention of the Architect any discrepancies between Detention Equipment Contractor’s shop drawings and the contract drawings that may occur during construction of the building shall be immediately reported to the Architect and the Detention Equipment Contractor for resolution. Other contractors shall not proceed with work affecting detention equipment until such discrepancies have been resolved.
  2. Embedded items of detention equipment are to be set in concrete or masonry by the General Contractor. These embedded items shall be furnished and delivered by the Detention Equipment Contractor F.O.B. his truck or common carrier, to the building site and there unloaded by the General Contractor so as not to delay the truck’s departure from the building site. General Contractor shall be responsible for the security of the detention equipment embedded times at the job site. Detention-type shower stalls are to be delivered at the same time as embedded items of detention equipment and are to be placed in the building by the General Contractor at the location where they are to be later installed by the Detention Equipment Contractor.
  3. General Contractor shall provide the required openings approximately 6’0” x 8’0” through the areas of the building where it is to be installed. Location of these openings shall be coordinated with the Detention Equipment Contractor.
  4. Detention Equipment Contractor shall deliver and be responsible for placing the building detention equipment that he is to install as part of this contract.
  5. Detention equipment installation shall not be started until the detention area is broom clean and properly lighted, exterior enclosing walls are in place, exterior windows glazed, and roof completely installed to prevent weather damage to the locking mechanisms and other mechanical parts of the detention equipment, and written notice is received by Detention Equipment contractor to inform the Architect (or General Contractor if detention equipment is a subcontract) stating that these conditions exist at the building site.
  6. General Contractor shall be entirely responsible for accuracy of building construction, such as locations of beams, columns and masonry walls and for accuracy in concrete work. Concrete ceiling must be level and true. Any chipping of concrete or pointing up between the detention steel and the concrete work that may be necessary due to unevenness of concrete will be done by the General Contractor in a manner acceptable to the Architect at no cost to the Detention Equipment Contractor.
  7. General Contractor shall complete all floor finish, concrete curbs, waterproofing and other concrete work, where shown or specified in connection with the detention equipment and all plastering and painting on or near detention equipment after detention equipment is completely erected in building.
  8. Detention Equipment Contractor will cut all necessary holes in steel detention equipment required for proper installation of plumbing, heating, and electrical and ventilation work. Holes are to be laid out with center punch marks on the detention equipment by the contractors requiring these holes, which will be cut by the Detention Equipment Contractor in strict accordance with these punch marks. Contractors requiring holes in steel detention equipment shall be responsible for proper location and sizes of holes. Changes required after holes have been cut shall be at the same expense of the contractor requiring such changes. Holes shall be laid out and cut during installation of the detention equipment and prior to finish painting.
  9. Plumbing Contractor shall furnish and install finished plumbing in detention areas. Shower drains, when specified as part of the detention equipment work, shall be furnished by the Detention Equipment Contractor but shall be installed by the Plumbing Contractor shall furnish and install showerheads and mixing valves for the detention-type steel shower stalls.
  10. Mechanical Contractor shall install heating and ventilation ducts where required in the detention areas after the detention equipment is erected in place. Any changes or modifications from the contract drawing and/or Detention Equipment Contractor’s approved shop drawings made by the Mechanical Contractor which affect security vents, grilles or other detention equipment shall be at the expense of the Mechanical Contractor. Detention Equipment Contractor shall be notified of such changes before they are made. The Mechanical Contractor shall reimburse the Detention Equipment Contractor for any additional expense resulting from such changes.
  11. Electrical Contractor shall furnish and install all field wiring and conduits and make all necessary field connections for the electrical operation of the detention equipment locking devices, electric locks, and controls therefore, in strict accordance with Detention Equipment Contractor’s approved electrical shop drawings. Electrical Contractor shall also furnish and install all necessary electrical components including, but not limited to, conduits, wiring and lamps and shall make all necessary connections for the detention type electric light fixtures which are specified to be furnished and installed by the Detention Equipment Contractor.
  12. All detention equipment herein specified, except aluminum, bronze, or stainless steel finish hardware and parts of the work to be enameled or plated, shall be painted on shop coat of rust resistant red oxide metallic primer, before shipping. Retouching of the shop coat of paint and finish painting of all detention equipment after erection and final adjustment of the detention equipment shall be done by the Painting Subcontractor, under the supervision of Detention Equipment Contractor. Burns, weld, and weld spatter on detention equipment caused by the Detention Equipment Contractor shall be thoroughly cleaned by the Detention Equipment Contractor. Mortar, plaster, concrete, waterproofing, dust and other foreign matter on the detention equipment shall be thoroughly cleaned by the General Contractor.